This Draft East African Standard specifies requirements for PVC-covered conductors for overhead power lines. These requirements are limited to the PVC covering and to the testing thereof after application to the conductors.
Two minimum thickness of covering have been standardized as follows.
Designation minimum thickness of covering
Type 8 0.8mm
Type 16 1.6mm
Type 8 is intended for use only where the operating voltage of the power line does not exceed 650 V r.m.s. between any two conductors or 250 V r.m.s. between any conductor and earth.
Under these operating conditions, it is suitable for:
a) crossing of telecommunication lines to guard against contact;
b) proximities to telecommunication lines to guard against contact; and
c) lines particularly service lines accessible from building.
Type 16 is intended for use only where the operating voltage of the power line exceeds 650 V r.m.s. between any two conductors or 250 V r.m.s. between any conductor and earth, but does not normally exceed 11 kV r.m.s. between conductors or 6.6 kV r.m.s. between any conductor and earth.The earthing of a neutral point of the system through an arc-suppression coil is not precluded if arrangements exist for clearing earth faults without undue delay under these operating conditions Type 16 is suitable for crossings of telecommunication lines and proximities to them.
These covered conductors shall not be used for any other purpose other than over-head lines.
Electric conductors, for a voltage > 1.000 V, insulated, n.e.s. (HS code(s): 854460); Electrical wires and cables in general (ICS code(s): 29.060.01): PVC Covered conductors